68L ISO9809-1 10.2M3 51KG 172bar 37MN CO2 Tanks Gas Cylinder
68L10.2M3 51KG 172bar 37MN ISO9809-1 CO2 tanks gas cylinder
Product Information:
1、68 litres of; 37 mn; Iso9809-1 production standard; 267mm cylinder outer diameter; Working pressure 150bar or 172bar; Hydrostatic test pressure 258bar;
2、Carbon dioxide cylinder body height 1480mm; Carbon dioxide bottle body weight 70.7KG;
The maximum liquid carbon dioxide charge is 51KG (9000 litres);
The minimum design wall thickness of oxygen cylinder is 6.2mm;
Carbon dioxide cylinder mouth thread PZ27.8; 25E; PZ39; 3/4-14 NGT, etc.;
3、Alias: 68L 172bar CO2 gas cylinders ,68L 172bar CO2 tanks ,51Kg CO2 cylinders,68L gas cylinders,172bar gas cylinders,Fire cylinders,68litre Fire cylinders; 68 litre carbon dioxide fire cylinder
68L ISO9809-1 10.2M3 51KG 172bar 37MN CO2 Tanks Gas Cylinder
1、Minimum order quantity: 100 only
2、Use cylinders:Our seamless steel cylinders are widely used in industry, medical devices, fire fighting and scientific research
3、We are China's gas cylinder production factory, product sales:China, Southeast Asia, Middle East, Asia, Africa, Europe, Oceania, America
4、Batch tests : All tests for checking the quality of the gas cylinder shall be carried out at the completion of cylinder manufacture, i.e. at any stage after the heat treatment.
5、For the purposes of batch testing, the manufacturer shall provide the inspector with: ⎯ the type approval certificate;
All rights reserved
⎯ the certificates stating the cast analysis of the steel supplied for the manufacture of the cylinders;
⎯ evidence that appropriate heat treatment has been performed;
⎯ the certificates showing the ultrasonic examination results;
⎯ a list of the cylinders, stating serial numbers and stamp markings, as required;
⎯ confirmation that threads have been checked in accordance with gauging requirements. The gauges to be used shall be specified
Tips for safe use of gas cylinders:
Carbon dioxide fire extinguishing system should be equipped with automatic control, manual control and mechanical emergency operation of three starting modes; Automatic control is not required when local fire extinguishing systems are used in frequently manned protected areas.
In the place where automatic fire alarm system shall be installed when the fire extinguishing system is installed, the action signal and related alarm signal, working state and control state of the carbon dioxide fire extinguishing system shall be displayed on the fire alarm controller.
Shandong Hongsheng Pressure Vessel Co., Ltd. is willing to be your long-term partner and chief cylinder safety officer, and jointly escort your cylinder safety.
6、68 litre Gas Cylinder Product Parameters table (ISO9809-1 150BAR)
68L ISO9809-1 10.2M3 51KG 172bar 37MN CO2 Tanks Gas Cylinder
Type | Outside Diameter (mm) | Water Capacity (L) | Bottle Height (mm) | Weight (kg) | Working pressure (Bar) | Design wall thickness (mm) | Material Grades |
ISO267-68.0L-150 | 267 | 68.0 | 1480 | 70.7 | 150 | 6.2 | 37MN |